AC Combiners & Recombiners
UL listed
(480 - 600VAC) 400 - 4000A
400 - 1000A
AC Combiners (480 - 600VAC)
(UL 891 Construction, UL 508A cert.), (MLO) Wall mount platform for 480 – 600VAC PV applications. Supporting up to (8) feeders. Multiple feeder breaker size options & combinations available, with bus ampacity sized at 1000A. MVT connection via cable. Thermally engineered NEMA 3R enclosure.
- Combines 2 – 8 string inverters
- 480 – 600VAC 3PH, 3W / 4W
- 400A – 800A bus rating, MLO
- 40 – 250A MCCB’s TM / ETU trip,
80% / 100% - Interrupt rating up to
50kAIC @ 600VAC, 50kAIC @480VAC - Incoming cable size to 350MCM
- Outgoing cable size 350 – 750MCM (2) cables per phase
400 - 1000A
Wall Mounted
AC Combiners (480 - 600VAC)
(UL 891 construction, UL 508A cert.), (MCB) or (MLO) wall mount platform for 480 – 600VAC PV applications. Supporting up to (10) feeders. Multiple feeder breaker size options & combinations available, with bus ampacity sized at 1500A. MVT connection via cable. Thermally engineered NEMA 3R enclosure.
- Wall Mounted (60″ X 36″ X 18″)
- 400 – 1000A Main / MLO
- 100% Rated Main % Feeder (Option
- Main Breaker LI / LSIG, LSIG W AERMS
- Feeder Ranges: 100, 150, 250AF
- Electronic Trip Main / Feeders
- Interrupt Ratings:
50kAIC @ 480VAC, 50kAIC @ 600VAC - Surge Suppressor Option
- Bottom Entry / Exit
- Optional Output CT’s
400 - 1200A Freestanding
AC Combiners (480 - 600VAC)
(UL 891 listed) (MCB) or (MLO) free standing platform for 480 – 600VAC PV applications. Supporting up to (14) feeders. Multiple feeder breaker size options & combinations available, with bus ampacity sized at 1500A. MVT connection via cable. Thermally engineered NEMA 3R enclosure.
- Freestanding (80″ X 42″ X 24″)
- 400 – 1200A Main / MLO
- 100% Rated Main % Feeder (Option)
- Main Breaker LI / LSIG, LSIG W AERMS
- Feeder Ranges: 100, 150, 250, 400, 600AF
- Electronic Trip Main / Feeders
- Interrupt Ratings:
65kAIC @ 480VAC, 50kAIC @ 600VAC - Surge Suppressor Option
- Bottom / Top / Side Entry Option
- Optional Output CT’s
1200- 4000A
AC Combiners (480 - 600VAC)
(UL 891 listed) (MCB) or (MLO) switchboard platform for 480 – 600VAC PV applications. Supporting up to (40) feeders in one switchboard. Multiple feeder breaker size options & combination are available, with bus ampacities from 1200 – 4000A. MVT connections available by direct bus or by cable. Thermally engineered NEMA 3R enclosure.
- 3PH, 4W (90″ x 60″ x 36″)
- 1200 – 4000A main breaker / bus rating options
- Drives up to 3,500kVA transformer @ 600VAC
- (MLO) option also available
- High density (up to 40 x 100AF) branch feeders
- Feeder ranges: 125, 150, 250, 400, 600, 800, 1000AF
- Interrupt Ratings: *Up To* 100kAIC @ 480VAC, 65kAIC @ 600VAC
- Surge suppressor option
- Oversized lug options for feeders available
- CT / PT / metering packages available