AC Combiners & Recombiners

UL Listed
(660 - 800VAC) 300 - 3000A

400A
Disconnect

AC Non-Fused Disconnect.
(660 - 800VAC)

(UL 508A Listed) Local AC inverter disconnect for 660-800VAC inverters. Non-fused disconnect. Thermally engineered NEMA 3R enclosure

  • 660 – 800VAC, 400A Local
  • 34″ X 17″ X 14″ Deep NEMA 3R Rackmount
  • *Up To* 600MCM / 1 Cable / Phase
  • *Up To* 350MCM / 2 Cable / Phase

300A MCCB Disconnect

AC Disconnect.
(660 - 800VAC)

(UL 508A Listed) Local AC inverter disconnect for 660-800VAC inverters. Non-fused disconnect. Thermally engineered NEMA 3R enclosure

  • 660 – 800VAC, 120 – 300A Circuit Breaker Disconnect
  • 34″ X 17″ X 14″ Deep NEMA 3R Rackmount
  • *Up To* 500MCM, 1 Cable / Phase
  • *Up To* 250MCM, 2 Cables / Phase
  • Electronic Trip MCCB, 35kAIC @ 800VAC

400 - 1000A
Rack Mount

AC Combiner (660 - 800VAC)

(UL 891 construction, UL 508A Cert.), (MLO) wall mount platform for 660- 800VAC PV applications. Supporting up to (4) feeders. Utilizes ABB T5X MCCB (adjustable from 120-300A. Bus ampacity up to 1000A. MVT connection via cable. Thermally engineered NEMA 3R enclosure.

  • Combines 2 – 4 inverters
  • Up To 4 MCCB’s 400AF / 120
  • 100% Rated, Electronic Trip
  • Incoming (From Inverter) Up To 500MCM 1/Phase
  • Outgoing Up To 750MCM , Up To 3/Phase 
  • Interrupt Rating 35kAIC
  • Options: Fans, Heater, CT’s

1200 - 3000A
(FS) (MLO)

AC Combiner (660 - 800VAC)

(UL 891 Listed), (MLO) freestanding SWBD 660 – 800VAC PV applications. Supporting up to (14) feeders. Feeders utilize ABB T5X MCCB (trip selectable from 120 – 300A), with bus ampacity sized at 1200 – 3000A. MVT connection via cable or direct bus.  Optional SEL 751A for secondary overcurrent protection (LSIG). Thermally engineered NEMA 3R enclosure.   

  • 800VAC, 3PH, 3W/4W, 90″ X 60″ X 32″
  • 3000A Bus, MLO, *Up To* 3000kVA Transformer
  • Up To (14) MCCB’s *Up To* 300A Ea. (100% Rated), TM *Or* ETU Trip, Adjustable From 120A To 300A
  • Cable *Or* Direct Bus Connection To MVT
  • UL Listed Main Protective Relay (751A), (LSIG, AERMS)
  • CT / PT / Revenue Grade Metering Option
  • Surge Suppressor Option
  • Thermal Management Options

1200 - 3000A
(FS) (MCB)

AC Combiner (660 - 800VAC)

(UL  891 Listed), (MCB) or (MLO) freestanding SWBD 660 – 800VAC PV applications. Supporting up to (20) feeders. Main breaker 1200 – 3000A, LSIG, AERMS. Feeders utilize ABB T5X MCCB (trip selectable from 120 – 300A). MVT connection via cable or direct bus. Thermally engineered NEMA 3R enclosure.

  • 800VAC, 3PH, 4W, 90″ X 60″ X 36″
  • 1200 – 3000A Bus, (MCB) Or (MLO), Up To 3000kVA Transformer
  • Interrupting Rating Of 35kALIC @ 800VAC
  • Cable *Or* Direct Bus Connection To MVT
  • UL Listed MCB (LSIG, AERMS)
  • CT / PT / Revenue Grade Metering Option
  • LSIG (SEL 751A) Optional For (MLO)
  • Surge Suppressor Option
  • Thermal Management Options

When It's Critical...
Have An EPEC Solution

Solar. Solutions. Simplified.

Quick Contact

Moving renewable power forward effectively and reliably with quick, simple solutions designed for solar from the ground up.

Head Office

Media

our Newsletter

Ⓒ 2022 by EPEC solutions, Inc.

800vac mccb infographic, epec solutions inc.